Feed-water analysis
TDS, hardness, alkalinity, silica, iron, manganese, SDI, temperature and microbiology affect pretreatment and membrane performance.
Engineering reference for industrial RO pretreatment, membrane selection, recovery, cleaning, scaling and troubleshooting.
Open detailed PDF guide Ask an engineer
TDS, hardness, alkalinity, silica, iron, manganese, SDI, temperature and microbiology affect pretreatment and membrane performance.
Media filtration, cartridge filtration, antiscalant and dechlorination are selected to protect the membrane array.
Normalise permeate flow and salt passage for temperature and pressure so fouling is distinguished from seasonal changes.
Cleaning chemistry must match the fouling type and membrane manufacturer limits; recovery targets must respect scaling and operating constraints.
Start with a representative raw-water laboratory report and confirm whether the source changes seasonally. At minimum, review conductivity or TDS, pH, temperature, hardness, alkalinity, silica, sulphate, chloride, iron, manganese, turbidity and SDI where applicable. The membrane projection should use the actual feed chemistry and required permeate quality, not a generic recovery assumption.
A sustained decline in normalized permeate flow, rising normalized salt passage or increasing pressure drop can indicate different failure modes. Compare trends against the commissioning baseline, check instrumentation and pretreatment first, and use the membrane manufacturer's cleaning criteria. Cleaning chemistry, pH, temperature and contact time must remain within the membrane supplier's limits. Do not increase recovery or dose chemicals blindly to compensate for a deteriorating plant.
Related resources: industrial RO plant services, RO chemicals, RO troubleshooting article and technical documents.